Description

The part number 1SQA700010R0001 corresponds to the ABB XB4HU3200AJJ00D4XX, which is an enclosed molded-case circuit breaker (MCCB). [1]
Key Specifications
Providing reliable overcurrent protection for industrial facilities, the ABB XT4HU3200AFJ000XXX operates within the SACE Tmax XT4 frame. This 3-pole, 200A breaker features a fixed thermal and fixed magnetic (TMF) trip unit to deliver consistent long-time and instantaneous defense. It mounts into ABB SACE Tmax XT panelboards and enclosures, serving as a direct replacement for legacy T4H200 breakers. Rated at 65kAIC at 480VAC, it includes load side lugs and current-limiting technology.
  • This is an ABB XT4N 250A Molded Case Circuit Breaker (MCCB) with a 3-pole configuration.
  • The breaker is designed for power distribution and features a thermal-magnetic trip unit.
  • It operates at a rated current of 250A and is part of the SACE Tmax XT series.
  • Specifications

    Brand ABB
    Series XT4
    Amperage 200A
    Voltage 240VAC, 480VAC, 600VAC, 250VDC, 600VDC
    Poles 3
    Phase 3
    AIC Rating 150kA @ 240VAC, 65kA @ 480VAC, 25kA @ 600VAC, 50kA @ 250VDC, 65kA @ 600VDC
    Mounting Style Unit Mount
    Terminal Type Lugs
    For Use With ABB SACE Tmax XT Panelboards, Switchboards, Enclosures
    Trip Technology Thermal Magnetic
    Trip Function Code LI
    Trip Function Long-Time, Instantaneous
    Trip Adjustability Fixed Thermal, Fixed Magnetic
    Wire Gauge 4 AWG - 300 kcmil (Cu/Al)
    Max Wire 300 kcmil
    Min Wire 4 AWG
    Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm, Padlock Attachment
    Accessories Load Side Lugs Included
    Standards CSA C22.2 No. 5, IEC 60947-2, UL 489
    Approval CCC, CSA, cULus, IEC, KEMA, RINA, UL
    Temp Rating -25C to 70C
    Construction Features Current Limiting, HACR Rated, Reverse Feed

Payment & Security

American Express Diners Club Discover JCB Klarna Maestro Mastercard PayPal Union Pay Visa

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.

Estimate shipping

Customer Reviews

Be the first to write a review
0%
(0)
0%
(0)
0%
(0)
0%
(0)
0%
(0)

You may also like

Recently Viewed